ACX-240
AC Current / Voltage  Two wire Transmitter

ACX-240 AC Current/Voltage 2wire Transmitter

 

ACX-240 AC Current / Voltage 2 wire Transmitter´Â »ê¾÷ ÇöÀå¿¡¼­ Àü±â°ü·Ã½Ã¼³À» Á¡°Ë, °ü¸®ÇϰíÀÚ ÇÒ °æ¿ì ±³·ù Àü·ù/Àü¾Ð½ÅÈ£¸¦ 4-20mA Ãâ·Â½ÅÈ£·Î Àü¼ÛÇÒ ¼ö ÀÖ´Â 2¼±½Ä Àü¼Û±âÀÔ´Ï´Ù.

¡á 2¼±½Ä 0-5Amp. 0-250Vac Transmitter
¡á ÁÖº¯¿Âµµ -31 ~ +85 µµ¾¾
¡á °íÁ¤È®µµ, °í ÀçÇö¼º ( ±0.25% )
¡á 350 millisec ÀÀ´ä¼º (10% - 90% step response)

»ç ¾ç

 

 

 

ÀԷ (Input) :

 

AC Current: Any 0-1 to 0-5 amps AC
AC Voltage: Any 0-0.25 to 0-250 VAC

Ãâ·Â(Output) :

 

4 ~ 20mA DC

Zero Adjustment:

 

±5% nominal of span

Course Span Adjustment:

 

100% of a major range(voltage only)

Fine Span Adjustment:

 

±5% nominal of majorrange (±1 Amp for current input)

Input Frequency Range:

 

25-1,000 Hz

Input Overload Capability:

 

200% continuous

Á¤È®µµ (Accuracy):

 

±0.25%

Independent Linearity:

 

±0.15% maximum,±0.06% typical

Repeatability:

 

±0.005% max., ±0.002% typ

Bandwidth:

 

(-3 db): 1 Hz

Power Supply Effect:

 

±0.005% of span, max.

Load Effect:

 

±0.005% zero to full loadOutput Ripple:

Isolation (Input-output-case) :

 

1000 VDC or 600 VAC

Output Ripple :

 

10 mV P/P maximum

ÁÖº¯¿Âµµ :

 

-31 ~ +85 degC

¿Âµµ ¿µÇâ :

 

Zero TC: ±0.01% of span max/°C
Span TC:+0.02% of span max/°C

Reponse Time(°»½ÅÁÖ±â) :

 

350 milliseconds,(10% to 90% step response)

Housing :

 

PA 6.6 (Polyamid Non- Reinforced)

Dimension (HWD) :

 

79 x 25 x 86 mm

¹«°Ô :

 

115 ±×·¥

Mounting :

 

Standard DIN rail

 

 

 

 



 



Ƽ¿¥¼Ö·ç¼Ç(ÁÖ) / ¼­¿ï½Ã ±Ýõ±¸ °¡»êµ¿ 426-5 (¿ùµå¸Þ¸£µð¾Óº¥Ã³¼¾Å¸2 ºôµù717È£) / Tel:(02)784-2526 / Fax:(02)784-2547